dn-60341:a1 • 2/9/10 — Page 1 of 2
SpectrAlert® Advance
Mini-Horns
MHR/MHW
Audio/Visual Devices
dn-60341:a1
General
The SpectrAlert® Advance series of mini-horn sounders are
designed to simplify installation to provide primary and sec-
ondary signaling for fire and security applications.
The MHR and MHW mini-horns operate at 12 and 24 volts and
are ideal for hotel, motel or residential fire system applications,
where a smaller notification device is desired. The mini-horns
offer high and low volume settings, and temporal or non-tem-
poral tones. The horns can be mounted to single gang back
boxes for aesthetically sensitive applications. Synchronization
is also provided when using the MDL3R, MDL3W module or
any Notifier panel with the System Sensor sync protocol.
The MHR and MHW mini-horns can operate between 32 and
120 degrees Fahrenheit from a regulated DC or full-wave recti-
fied, unfiltered power supply. They are listed to Underwriter’s
Laboratories.
Features
Standard UL 464 for fire protective signaling systems.
12 and 24V operation.
High and low volume settings.
Temporal and non-temporal tones.
Mounts to a single-gang backbox.
Compatible with MDL sync module.
Mechanically and electrically compatible with PA400 series
Mini-Alert™ sounders.
Specifications
PHYSICAL SPECIALIZATIONS
Dimensions: 4.6”L x 2.9”W x .45”D.
Weight: 2.67 oz.
Operating Temperature Range: 0°C to 49°C
(32°F to 120°F)
.
Mounting: Surface: Deep single-gang backbox (2-3/4” deep);
Flush: Standard 4” x 4” back box.
ELECTRICAL SPECIFICATIONS
Input Terminals: 12 to 18 AWG
Nominal Voltage: Regulated 12DC/FWR or 24DC/FWR
Operating Voltage: 8-33
Operating Voltage with MDL3R/W: 9-33
Architectural/Engineering
Specifications
Mini-horns shall be a System Sensor Model MHR or MHW
capable of operating at nominal 12 or 24VDC and shall mount
to a single gang back box. Mini-horns shall be listed to Under-
writer’s Laboratories Standard UL464 for fire protective signal-
ing systems. Mini-horns shall operate between 32 and 120
degrees Fahrenheit from a regulated DC, or full-wave rectified,
unfiltered power supply. When used with the Sync•Circuit™
Module, 12-volt rated notification appliance circuit outputs
shall operate between nine and 17.5 volts; 24-volt rated notifi-
cation appliance circuit outputs shall operate between 17 and
33 volts.
Listings and Approvals
These listings and approvals apply to the modules specified in
this document. In some cases, certain modules or applications
may not be listed by certain approval agencies, or listing may
be in progress. Consult factory for listing status.
UL Listed: S4011
MEA: 7-07-E
CSFM: 7135-1653:196
FM Approved: 3028007
Ordering Information
MHR: Mini-Horn; Red.
MHW: Mini-Horn; White.
60296pho1.jpg
Zobrazit stránku 0
1 2

Shrnutí obsahu

Strany 1 - Mini-Horns

dn-60341:a1 • 2/9/10 — Page 1 of 2SpectrAlert® AdvanceMini-HornsMHR/MHWAudio/Visual Devicesdn-60341:a1GeneralThe SpectrAlert® Advance series of mini-h

Strany 2

Page 2 of 2 — dn-60341:a1 • 2/9/10SpectrAlert® is a registered trademark and Mini-Alert™ is a trademark ofHoneywell International Inc. ©2010 by Honeyw

Příbuzné modely Mini-Horns MHR

Komentáře k této Příručce

Žádné komentáře